Acetylene cylinders are not designed for use in environments where the temperatures may exceed 52ºc 125ºf.
Oxygen and acetylene cylinder storage requirements.
In the storage facility both types of cylinders must be kept separate.
6 m or by a barrier of noncombustible material at least 5 ft.
Risks and hazards of acetylene and oxygen gases.
In general industry workplaces oxygen and acetylene cylinders that are in use or are connected for use will not be considered to be in storage for purposes of the 1910 253 storage requirements 1 osha also will not cite a general industry employer if a single oxygen cylinder and a single acetylene cylinder are maintained with their cylinder valves closed and valve protection caps affixed.
Take care to store small cylinders properly as they don t have protection caps on them.
Up to 300 ft3 approximately 12 13 e cylinders is permitted to be stored within a 22 500 ft2area without requiring to be in a special storage location.
Nfpa 51 2 4 3 oxygen cylinders in storage shall be separated from fuel gas cylinders or combustible materials especially oil or grease by a minimum distance of 20 ft.
1910 253 b 4 iv.
Acetylene cylinders and oxygen cylinders both have their own unique risks and hazards and must never be stored together as they can react dangerously with one another.
Indoors separate oxygen from fuel gas cylinders by at least 6 1 m 20 ft or by a wall at least 1 5 m 5 ft high with a minimum half hour fire resistance.
Store oxygen cylinders and fuel gas cylinders separately.
Acetylene cylinders must be always stored in the upright position with valve caps on.
1926 350 a 10 oxygen cylinders in storage shall be separated from fuel gas cylinders or combustible materials especially oil or grease a minimum distance of 20 feet 6 1 m or by a noncombustible barrier at least 5 feet 1 5 m high having a fire resistance rating of at least one half hour.
We look at both separately below.
Csa w117 2 12 r 2017 safety in welding cutting and allied processes.
Storage for safety purposes oxygen and acetylene cylinders have to be stored a minimum of 10 feet from each other.
Local jurisdiction requirements may vary.
1 5 m high having a fire resistance rating of at least 1 2 hour.
But is this assumption correct.
Cylinders that are in use or available for immediate use do not need to be included in this determination.
Oxygen cylinders in storage shall be separated from fuel gas cylinders or combustible materials especially oil or grease a minimum distance of 20 feet 6 1 m or by a noncombustible barrier at least 5 feet 1 5 m high having a fire resistance rating of at least one half hour.
The general industry and construction standards only specify the requirements for storage and use but not how long the oxygen and acetylene cylinders sits idle before it s considered in storage.
Twenty four hours of inactivity is the answer that i frequently hear.